RAPS - Remote Area Power System
| RAPS - Remote Area Power System | ||||
| KVA | 5kVA ~ 150kVA | |||
| INPUT VOLTAGE DC | ||||
| Input Voltage | 48V / 120V / 240V / 400V | |||
| Input Range | + / - 12.5% | |||
| BYPASS AC INPUT | ||||
| Input Voltage | 120V / 240V + / - 10% 1 Phase or415V + / - 10% 3 Phase | |||
| Input Frequency | 50 60 Hz + / - 5% | |||
| Transfer Time | <1 millisecond | |||
| OUTPUT AC | ||||
| Output Voltage | 120V / 240V 1 Phase or 415V 3 Phase | |||
| Wave Form | Sine Wave | |||
| Output Power Factor | 0.8 | |||
| Frequency Range | 50 / 60 Hz Synchronization With Bypass or + / - 0.5Hz Free Running | |||
| Frequency Slew Rate | 1 Hz/sec | |||
| Voltage Regulation | + / - 1% Steady State | |||
| Tolerance | 1% Balanced Load2% Un-Balanced Load | |||
| Crest Factor | 3:1 | |||
| THD | < 2% max. Linear Load<2% Single Harmonic<5% Non Linear Load | |||
| Overload | 125% | 15 Minutes | ||
| 150% | Shut Down | |||
| Efficiency (100% Load) | >92% at Full Load | |||
| STATIC SWITCH | ||||
| Overload Rating | 200% for 10 Minutes, 1000% for 1 Cycle | |||
| Mains / Inverter | 1 millisecond, no break transfer | |||
| OVERALL CHARACTERISTICS | ||||
| Height x Width x Depth (mm) | 1300 x 800 x 400 | 1520 x 820 x 610 | 1770 x 1000 x 760 | |
| Weight (Kg) | 100kg ~ 1000kg | |||
| Audible Noise | < 58 dBA (at 1 Meter) | |||
| Temperature | 0 - 40°C | |||
| Humidity | 0 – 90% (Non-Condensing) | |||
| Altitude | <1600 M Above Sea Level | |||
| Maintenance Bypass Switch | Internal ~ No Break Switch | |||
| Protection | Under/Over Voltage, Overload, Over Temperature, Internal Malfunction, etc | |||
| MTBF | 30,000 Hours | |||
| Cable Enrty | Top or Bottom | |||
| Cubicle | Free Standing, Powder Coated | |||
| LED,LCD,Buzzer | YES | |||
| Remote Control / Communication Interface | Voltage Free Dry Contacts, RS232 | |||
| . Different specifications required are available. | ||||